Envatronics Vietnam, ENVA-3015 PH, ENVA-3015 PH Envatronics Vietnam, đại lý Envatronics Vietnam
|
Measuring
Object |
Hydrogen Ion Concentration(pH) Oxidation Reduction Potential(ORP) |
|
Measuring
Principle |
Glass Electrode Method |
|
Measuring
Range |
0.00~14.00pH, ±999mv |
|
Measuring
Condition |
Flow Rate : Submersion Max 2m/sec ----------- Flow through 3~11 L/min Conductivity : Min 50us/cm Oper'Temp : Max.120℃ Oper'Pressure : Max.100PSI |
|
PH Indication Controller
|
|
|
Model
|
ENVA-3015 |
|
Measuring
Range |
0.00~14.00pH, ±999mv |
|
Display
Method |
7-Segment 3 1/2 Digt |
|
Alarm Setting
|
High, Low 2ponint V.R.Set |
|
Mode Selection
|
Tact Switch |
|
Transmission
Signal |
DC 4~20mA(R.Load 750Ω Max.) / RS 485통신 |
|
Transmission
Signal Range |
User Ordering Sheet |
|
Power Supply
& Consumption |
AC 100V 50/60Hz ±10% 3VA AC 220V 50/60Hz ±10% 3VA |
|
Ambient
Temperature |
-5~45℃ |
|
Construction
|
DIN96 Panel Mount Type |
|
Replay Contact
|
1alb AC250V 5A(R.Load) |
|
Weight
|
Approx. 450g |
|
Functional
Specification |
Temperature Compensation : -5~100℃ ZERO Adjusting : pH7 ± 1.5pH SPAN Adjusting : pH4 ± 1.5pH Accuracy : ±0.02pH Repeatability : 0.02pH Response Time : Within 10sec(90%) |